Permit Number:
02 5465
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
1076 OCEAN DOCK RD Anchorage
Location:
Work Description:
Work Descr: building pump pit, Remarks: cs **note Storm Water still needs to be paid $300.00 10/02/02.**
Status:
Expired
Project Name:
Review Type:
Fire
Result:
Approved
Result Date:
9/12/2002 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): Provide details of 7,000 gallon tank to include normal and emergency venting, UL listing etc. C(2): FIRE PROTECTION SYSTEMS - Permits: Submit plans and apply for separate review and permits for Foam System and Fire Detection System. C(3): Provide electrical plans to show emergency lighting . C(4): FIRE REVIEW STATUS: DISAPPROVED 5/24/02 Carpenter C(5): Resubmittal 5/30/02: Tank submittal provided. No normal vent is shown to exterior of structure. This shall be sized to filling or withdrawal rate UFC7902. C(6): FIRE REVIEW STATUS: Approved for F and F only. No other approvals. 6/10/02 Carpenter C(7): 7/14/02 Received Electrical Plans: No Emergency lighting shown. FIRE REVIEW STATUS: F&F and SHELL. and Arch -No other approvals. Carpenter 7/9/02 . C(8): Per fire folder, FC approved electrical on 7/10/02. Plumbing and mechanical still outstanding. 8/14/02 CH
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501