Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
00 6194
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
2751 DEBARR RD Anchorage
Location:
Work Description:
Work Descr: Tenant Improvement RD, Remarks:
Status:
Expired
Project Name:
Review Type:
Structural
Result:
Approved
Result Date:
12/28/2000 10:04:59 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
C(1): Per discussion with engineer, please provide missing "GE" drawings, and provide calcs for the new roof beams. Please provide connection details for allbeams.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501