Permit Number:
00 6161
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
Work Descr: Tenant improvement 5/3/01 - dbl chg sprinkler system that was installed w/o permit per t. furch (fire) /td, Remarks: (nth)
Status:
Expired
Project Name:
DELTA AIRLINES RENOVATION
Review Type:
Electrical
Result:
Approved
Result Date:
1/5/2001 9:36:07 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): The following comments are based on the 1999 National Electrical Code and should be resolved before a permit is issued. This correction list is not a building permit. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local amendments to these codes. C(2): Sheet E5.0 - The AC-2 is not indicated on panel pin. Please indicate the electrical rating and the over current protection. C(3): Sheet E5.0 - Panel pin. The connected load is provided . Please provide the NEC demand load factor. C(4): ELECTRICAL STATUS: CORRECTIONS REQUIRED