Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: Tenant improvement 5/3/01 - dbl chg sprinkler system that was installed w/o permit per t. furch (fire) /td, Remarks: (nth)
Status: Expired
Project Name: DELTA AIRLINES RENOVATION
Review Type: Architectural
Result: Approved
Result Date: 12/26/2000 10:29:14 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Please provide manufacturers verification that paint called out on the F.T. plywood will not void the fire rating. UAC 302.3. C(2): Please see detail 9 A2.1 and UBC 706.1. Please update detail to show how joint will accommodate expected building movement and resist the passage of fire and hot gases. C(3): Please show the attachment of the new wall in detail 3 A 1.1 to resist not less than 5 psf per UBC 1611.5.