Permit Number:
00 5870
Permit Type:
Commercial Building Permit - None BldgNew
Address:
4301 DEBARR RD Anchorage
Location:
Work Description:
Work Descr: 15,090 sq ft New Carquest (B & C Auto Supply), Remarks: mf
Status:
Expired
Project Name:
CARQUEST/B&C AUTO
Review Type:
Fire
Result:
Correction
Result Date:
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): Please provide flow data for the three hydrants noted on the site plan. UFC 903.3 C(2): What activities will be conducted in the ["Work Room"] to require the one hour occupancy separation for the room? C(3): Please provide cutsheets and the location of the proposed wall hydrant. C(4): The area marked "Inv 101"has 15 foot storage devices. This high piled combustible storage must meet the requirements of Article 81 of the Uniform Fire Code, Article 81. Please submit a detailed proposed inventory for this storage area so that the commodity class may be determined. UFC 81 C(5): Separate permits will be needed for the sprinkler system and the fire alarm system. UFC 1001.3 C(6): FIRE PLAN RVW STATUS: Disapproved 10/27/00 k. foster