Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
00 5571
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
6200 BOEING AVE Anchorage
Location:
Work Description:
Work Descr: Tenant Improvement Office / Vehicle Maintenance, Remarks: mf **11/12/04 Jeff Lintelman of USKH will work on closing file***
Status:
Issued
Project Name:
NORTHWEST, #B
Review Type:
Fire
Result:
Approved
Result Date:
7/20/2000 1:47:49 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): Provide locations of occupancy separation walls. Also openings shall be protected with 1 hr doors. C(2): Offices that may have public access shall not exit through more hazardous area of Plant Work Area 108. C(3): Welding: Provide details of and compliance with UFC Article 49. Are there to be compressed welding gases arc welding etc.?? Welding area shall have a 2A20BC fire extinguisher. C(4): Verify/provide air handler shut-down by smoke-detection per mechanical code. C(5): Spray Booth: Shall be review and permitted before installation. C(6): FIRE REVIEW STATUS: DISAPPROVED 7/13/00 CARPENTER