Permit Number: 00 5570
Permit Type: Commercial Building Permit - None BldgAlter
Address: 6200 BOEING AVE Anchorage
Location:
Work Description: Work Descr: Tenant Build-Out. Office Vehicle Storage, Remarks: mf 9/11/00 - elec upgrade issued to this permit should have been issued on #00-5571, transferred permit today /td *11/12/04 Jeff Lintelman of USKH will work on closing this permit*
Status: Issued
Project Name: NORTHWEST, A1
Review Type: Structural
Result: Correction
Result Date:

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): These comments refer to Change Order #8, for seismic restraint of tanks. Review of this change order is based on the requirements of the 1997 Uniform Building Code and all adopted references thereto, as amended by MOA. The following comments must be addressed before these changes can be approved. C(2): Please provide engineering calcs. for design of the restraints. The sizes of the tanks aren't clear on the drawings and it isn't clear if straps are required for the 7500 gal. tank or what the net overturning forces are for the tanks.