Permit Number: 98 6185
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: demo and remodel of existing space for pen-air/era relocation of contract "c"/ checked in by Ross/gjs--Demo for non-sturctural app c. kustin 02-2-99-cah, Remarks: permittype =ALT/BAGGAGE CLAIM, status= FINAL 10/22/99, planstatus=
Status: Closed
Project Name: BAGGAGE CLAIM PENN AIR/ERA
Review Type: Plumbing
Result: Approved
Result Date: 2/11/1999 8:46:59 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. . The following comments based on the 1994 Uniform plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform plumbing Code or any federal, state or local regulations. The following comments based on the 1994 Uniform plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform plumbing Code or any federal, state or local regulations. Reference the oil/water separator "clean water side vent". All vents must extend thru the roof per section 906.1. please address. STATUS: ADDRESSED 2-11-99. Reference the oil/water separator "clean water side vent". All vents must extend thru the roof per section 906.1. please address. STATUS: ADDRESSED 2-11-99