Permit Number:
97 5470
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
2751 DEBARR RD Anchorage
Location:
Work Description:
Work Descr: tenant improvement for common waiting, Remarks: no val see master file 96-5215 permittype =ALT OFFICE, status= CLOSED 9/9/97, planstatus=
Status:
Closed
Project Name:
COMMON WAITING ROOM
Review Type:
Electrical
Result:
Correction
Result Date:
6/9/1997 9:30:16 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. . Refererence Permit #97-5481 for comments on Power single line diagram and panel schedule for 3L. Refererence Permit #97-5481 for comments on Power single line diagram and panel schedule for 3L. Provide Egress lighitng fo rmain corridor per UBC 101. Provide Egress lighitng fo rmain corridor per UBC 101. Branch circuit not shown for corridor lights type `K' and `L', please revise and provide. Branch circuit not shown for corridor lights type `K' and `L', please revise and provide. Inspector to field verify that all electrical equipment in electrical room has required clearance per NEC 110-16 and 384-4. No response necessary. Inspector to field verify that all electrical equipment in electrical room has required clearance per NEC 110-16 and 384-4. No response necessary