Project Name: ALASKA RADIOLOGY
Review Type: Electrical
Result: Approved
Result Date: 6/6/1997 1:57:25 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. . The drawings do not specifically call an equipment grounding conductor as required in conduits per MOA amended revisions to NEC 250-91(b). Please provide indication that this is being addressed. The drawings do not specifically call an equipment grounding conductor as required in conduits per MOA amended revisions to NEC 250-91(b). Please provide indication that this is being addressed. Please provide emergency egress lighting for corridor serviced by branch circuit 3H9 (north/west on sheet TE2.3. Please provide emergency egress lighting for corridor serviced by branch circuit 3H9 (north/west on sheet TE2.3. Please provide calculations or additonal egress "bug-eye" for corridor serviced by branch circuit 3H42 (S/E on sheet TE2.3) to provide 1fc of egress lighting per UBC 101. Please provide calculations or additonal egress "bug-eye" for corridor serviced by branch circuit 3H42 (S/E on sheet TE2.3) to provide 1fc of egress lighting per UBC 101. Sheet TE3.3 - cannot determine the purpose of the exterior receptacles that are circuited to a junction box, no branch circuitry to a panel is shown. Please clarify. Sheet TE3.3 - cannot determine the purpose of the exterior receptacles that are circuited to a junction box, no branch circuitry to a panel is shown. Please clarify
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS