Permit Number: 08 5323
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: Reconstruct customer service counters in secured area; construct a couple of separtition walls, Remarks: tb
Status: Closed
Project Name: ALASKA AIRLINES
Review Type: Mechanical
Result: Approved
Result Date: 3/19/2009 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): 4/M3 The relocated electric range requires a vent hood with exhaust to the exterior of the building. (local amendment to IMC 505.10) C(2): 4/M3 Note #6 instructs to contractor to rebalance the exhaust outlet to 200 CFM. Between that and the kitchen exhaust hood venting to the exterior (comment #1) the total exhaust could be 300 CFM or more. Please clarify the path for the makeup air to enter the Kitchen 101 area. (IMC 501.3)