Permit Number: 08 5067
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Work Descr: tenant improvement, Remarks: JRD **OK for Greg Todd to p/u bldg permit per Bo w/ H Watt & Scott**tb **Ok for Jacob Burzinski to p/u plbg & mech permit per Jeff Hatt**tb
Status: Closed
Project Name: DAIRY QUEEN - ORANGE JULIUS
Review Type: Mechanical
Result: Approved
Result Date: 12/15/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Provide structural, seismic and wind load calculations as applicable plus fastening details for AC-1 and WH-1 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 12-15-08. C(2): Provide a roof top plan with the location of AC-1 and adjacent vents and exhaust fans to verify proper clearances from the outside air intake per IMC 401.4.1. RESOLVED PER RESUBMITTAL RECEIVED 12-15-08.