Permit Number:
07 5726
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
Work Descr: phase 2 seismic/structural upgrades for b - hex b concourse, food court an dticketing portion of south terminal building and remodel of all areas identified, Remarks: jrd
Status:
Closed
Project Name:
ANC SOUTH TERMINAL SEISMIC & S
Review Type:
Mechanical
Result:
Approved
Result Date:
3/23/2009 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): Provide structural and seismic calculations plus fastening details for RF-009 and SF-008 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 3-23-09. C(2): M7.16 Sheet note #8 states "Encase Plenum For Slot Diffuser In A Fire Rated GYP Enclosure". There is a fire damper to only one of four diffusers in the area. Architectural provides no information for that area. Please provide clarifying details and coordinate with architectural since this would require architectural details as well. RESOLVED PER RESUBMITTAL RECEIVED 3-23-09.