Permit Number: 07 5726
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: phase 2 seismic/structural upgrades for b - hex b concourse, food court an dticketing portion of south terminal building and remodel of all areas identified, Remarks: jrd
Status: Closed
Project Name: ANC SOUTH TERMINAL SEISMIC & S
Review Type: Electrical
Result: Approved
Result Date: 3/3/2009 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments are based on the 2005 National Electrical Code (NEC), and should be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC, or any federal, state or local amendments to these codes. C(2): The scope of work is to add two doors for the electrical room that houses electrical panel that exceeds 1200 Amperes. Please provide a layout for the two doors. Refer to NEC Section 110.26(C)(2).