Permit Number: 07 5726
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: phase 2 seismic/structural upgrades for b - hex b concourse, food court an dticketing portion of south terminal building and remodel of all areas identified, Remarks: jrd
Status: Closed
Project Name: ANC SOUTH TERMINAL SEISMIC & S
Review Type: Fire
Result: Approved
Result Date: 10/29/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments are based on the 2006 International Fire Code (IFC), the 2006 International Building Code (IBC) and state and local amendments and must be resolved before a permit is issued. The approval of plans and specifications does not permitthe violation of any section of the IFC, IBC or any federal, state or local regulations. C(2): Reference design Memo 57, page 2 of 2. Please note that item #3A indicates the fire alarm control module for signaling door release at DBC T15-01 controlling door SA 1282 will be deleted. All delayed egress doors and or security doors are required to be released upon activation of the fire alarm. Please verify. IFC 1008.1.8.6