Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
07 5247
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
Work Descr: T/I WITHIN EXISTING 'C' CORCOUSE, Remarks: JRD
Status:
Closed
Project Name:
ADMINISTRATION BUILDING
Review Type:
Structural
Result:
Approved
Result Date:
10/25/2007 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): PERMIT STATUS 10/15/2007 - C.O. #4 - Initial review. Comments issued. 10/25/2007 - Approved. C(2): RESPONSE COEFFICIENT FOR CONCRETE ANCHORAGE Refer to Calculations Page 2, 9. The design calls for Rp = 5.0 in accordance with ASCE 7 Table 9.6.3.2 for "General Electrical" equipment. However, the details call for 3/8 inch anchors with 2-1/2 inch embedment, which qualifies as a shallow anchor. ASCE 7 Section 9.6.1.6 requires the design of anchorage to concrete or masonry to be based on Rp = 1.5. Please provide revised calculations and details as necessary. Reference: ASCE 7 Section 9.6.1.6.1 Comment has been resolved. 10/25/07 MMP
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501