Permit Number: 06 6130
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: Work Descr: Add standby generator and relocate radiators to roof, Remarks: gjs
Status: Closed
Project Name: AK REGIONAL DR/GEN
Review Type: Structural
Result: Approved
Result Date: 9/29/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): PERMIT STATUS 9/25/2008 - C.O. #6 - Initial review. Comments issued. 9/29/2008 - Approved. C(2): PROTECTION OF REINFORCING The plans call for cutting of the slab areas of the waffle slab for the duct penetrations. It could not be determined if the ductwork is continuous through the slab openings. The concern is that the system could draw significant moisture through the opening and potentially corroding exposed reinforcing. Please advise if the ducts are continuous past the openings,or provide a means for protecting the exposed reinforcing. Reference: 9/29/08 - Resolved. Revised detail shows applied waterproofing membrane along all cut edges of concrete. MMP