| Date | Status | Code | Description | Ref | Location | Comments |
| 10/21/2026 | | Correct Below | * | | Service. | Label with available fault current and date calculated. |
| 10/21/2026 | | Correct Below | * | | Snow melt contactors and controllers. | 5KA SCCR rated units. UPDATE: ENGINEER HAS DETERMINED THAT ADDING 51FT OF CONDUCTOR WILL REDUCE THE AVAILABLE FAULT CURRENT TO 5KA OR BELOW. |
| 10/20/2026 | Corrected | Correct Below | * | | Pool water heaters. | 2-pole GFCI breakers do not trip with test button. |
| 10/20/2026 | Transfer | Correct Below | * | | "Aqua Creek" wireless controller. | Not listed. UPDATE: THESE DEVICES ARE BATTERY CHARGERS FOR THE ELECTRICALLY POWERED POOL LIFTS. OBTAIN LISTED BATTERY CHARGERS. ALSO, VERIFY THAT POOL LIFTS ARE LISTED OR OPERATE AT BELOW THE LOW VOLTAGE CONTACT LIMIT. |
| 10/20/2026 | | Correct Below | * | | Pool pump motors. | Units do not have overload protection. UPDATE: POOL PUMP MOTORS ARE TO BE LOCKED OUT OR DISCONNECTED FROM BREAKERS UNTIL OVERLOAD PROTECTION CAN BE INSTALLED. |
| 10/20/2026 | Corrected | Correct Below | * | | Pool area lighting. | Requires GFCI protection per 680.22(B). |
| 10/20/2026 | Corrected | Correct Below | * | | Fan coil units with field installed electric heating elements. | Manufacturer's UL rep needs to contact inspector about fan motor protection with larger breaker. UPDATE: CONTACT AT UL CONFIRMED THAT METHOD OF PROTECTION IS WITHIN THE LISTING OF THE FCUs. |