Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 924761
Inspection Type: Final Mechanical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/19/2026 MechFinalSee commentsSee Inspector Comments2nd fl West end of corridorS/A branch flex connection disconnected/joint missing sealant.
10/19/2026 MechFinalSee commentsSee Inspector Commentsfls 1-4 mech/storage/engineer's rmsT/A duct missing FRDs.
10/19/2026 MechFinalSee commentsSee Inspector Comments1st fl guest laundryDryer duct & gas connections incomplete.
10/19/2026 MechFinalSee commentsSee Inspector CommentsPool mech room EF-8Joint sealant missing at flex connections.
10/19/2026 MechFinalSee commentsSee Inspector CommentsPool mech roomAs per 2018 IMC 1006.6 note 11 relief valves shall not have a threaded connection.
10/19/2026 MechFinalSee commentsSee Inspector CommentsPool mech roomProvide installation manual for pool heaters.