| Date | Status | Code | Description | Ref | Location | Comments |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | 2nd fl West end of corridor | S/A branch flex connection disconnected/joint missing sealant. |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | fls 1-4 mech/storage/engineer's rms | T/A duct missing FRDs. |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | 1st fl guest laundry | Dryer duct & gas connections incomplete. |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | Pool mech room EF-8 | Joint sealant missing at flex connections. |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | Pool mech room | As per 2018 IMC 1006.6 note 11 relief valves shall not have a threaded connection. |
| 10/19/2026 | | MechFinal | See comments | See Inspector Comments | Pool mech room | Provide installation manual for pool heaters. |