Inspection #: 924155
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Elevator Inspection Requested by: Ryan Heaton 9078546593 rmh@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/20/2026TransferCorrect Below* Pool water heaters.2-pole GFCI breakers do not trip with test button.
10/20/2026TransferCorrect Below* "Aqua Creek" wireless controller.Not listed.
10/20/2026TransferCorrect Below* Pool pump motors.Units do not have overload protection.
10/20/2026TransferCorrect Below* Pool area lighting.Requires GFCI protection per 680.22(B).
10/20/2026TransferCorrect Below* Fan coil units with field installed electric heating elements.Manufacturer's UL rep needs to contact inspector about fan motor protection with larger breaker.
10/15/2026TransferCorrect Below* Remote exterior heads.Blanked-off until fixtures arrive.
10/15/2026TransferCorrect Below* Rooftop working clearance violations.110.26 violated at electrical compartments of large RTUs, freezer condenser, Captive Air, possibly other.
10/15/2026TransferCorrect Below* Domestic water boost pump industrial control panel.Piping violates 110.26 working clearance.
10/15/2026TransferCorrect Below* Snow melt contactors and controllers.Snow melt contactors are labelled with a 5KA short circuit current rating. Check controllers for short circuit current rating. Need to determine available fault current at this equipment.
10/15/2026CorrectedCorrect Below* Series rating labelling.Required per 110.22 at panels. Will verify that fault current at panels does not exceed series rating.