| Date | Status | Code | Description | Ref | Location | Comments |
| 10/20/2026 | Transfer | Correct Below | * | | Pool water heaters. | 2-pole GFCI breakers do not trip with test button. |
| 10/20/2026 | Transfer | Correct Below | * | | "Aqua Creek" wireless controller. | Not listed. |
| 10/20/2026 | Transfer | Correct Below | * | | Pool pump motors. | Units do not have overload protection. |
| 10/20/2026 | Transfer | Correct Below | * | | Pool area lighting. | Requires GFCI protection per 680.22(B). |
| 10/20/2026 | Transfer | Correct Below | * | | Fan coil units with field installed electric heating elements. | Manufacturer's UL rep needs to contact inspector about fan motor protection with larger breaker. |
| 10/15/2026 | Transfer | Correct Below | * | | Remote exterior heads. | Blanked-off until fixtures arrive. |
| 10/15/2026 | Transfer | Correct Below | * | | Rooftop working clearance violations. | 110.26 violated at electrical compartments of large RTUs, freezer condenser, Captive Air, possibly other. |
| 10/15/2026 | Transfer | Correct Below | * | | Domestic water boost pump industrial control panel. | Piping violates 110.26 working clearance. |
| 10/15/2026 | Transfer | Correct Below | * | | Snow melt contactors and controllers. | Snow melt contactors are labelled with a 5KA short circuit current rating. Check controllers for short circuit current rating. Need to determine available fault current at this equipment. |
| 10/15/2026 | Corrected | Correct Below | * | | Series rating labelling. | Required per 110.22 at panels. Will verify that fault current at panels does not exceed series rating. |