| Date | Status | Code | Description | Ref | Location | Comments |
| 10/8/2026 | | Correct Below | * | | Remote exterior heads. | not installed. |
| 10/8/2026 | Transfer | Correct Below | * | | Pool area. | Not complete. |
| 10/8/2026 | Transfer | Correct Below | * | | EV chargers. | 1. 625.21 requires OCPD to be 125% of max rating. 2. What sort of personnel protection system is included in the charger? See 2011 NEC 625.22. |
| 10/5/2026 | Transfer | Correct Below | * | | Fan coil units with field installed electric heating elements. | Fan requires 15A OCPD. Heating elements from 5KW to 8KW. Branch circuit breakers 30A to 45A. How are fan motors protected? Instructions seem to show some sort of internal OCPD that has not been installed. |
| 10/5/2026 | Transfer | Correct Below | * | | Corrections from inspection # 92106. | Various 1st floor and rooftop corrections not carried forward to this inspection. |
| 10/5/2026 | Transfer | Correct Below | * | | Lobby sconces. | Require bulbs for testing. |
| 10/5/2026 | Transfer | Correct Below | * | | Lobby floor receptacles. | Not installed. |
| 10/5/2026 | Transfer | Correct Below | * | | Lobby chandaliers. | Not installed. |
| 10/5/2026 | Corrected | Correct Below | * | | Receptacles on Lobby side of bar. | Receptacles within 6ft of sink require GFCI protection. |
| 10/5/2026 | Corrected | Correct Below | * | | Landscape sprinkler controller. | No apparent listing mark. |
| 10/5/2026 | Corrected | Correct Below | * | | Mixing valve controller. (Nexa Intellistation) | No apparent listing mark. |
| 10/5/2026 | Transfer | Correct Below | * | | Domestic water boost pump, industrial control panel. | Floor drain pipe and possibly other piping violates 110.26 working clearances. |