| Date | Status | Code | Description | Ref | Location | Comments |
| 10/6/2026 | | Firealarm19 | Correction(s) #6 | <div>Correct the following item(s):</div><div><br></div> | | 1st floor hall west end by door dividing rooms from business occupancy 2 horn strobes need to be relocated so that they can be seen to comply with corridor space on each side of the door.<div>2nd and 3rd floor hall strobe by elevator need to relocate to soffit in hall so it can be seen to comply with corridor spacing.</div><div>4th floor hall strobe by elevator need to relocate to soffit in hall so it can be seen to comply with corridor spacing and 3rd strobe in hall way need to be lowered to be seen.</div><div><br></div> |
| 10/6/2026 | | Firealarm20 | Correction(s) #7 | <div>Correct the following item(s):</div><div><br></div> | | Complete installation on horn strobes in vending area on floor 2,3 and 4 |
| 10/6/2026 | | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Okay for C.C.O. for 2 weeks (10/20/26) |
| 10/6/2026 | | Firealarm18 | Correction(s) #5 | <div>Correct the following item(s):</div><div><br></div> | | RTU units are not connected to Fire Alarm, complete installation |
| 10/6/2026 | | Firealarm16 | Correction(s) #3 | <div>Correct the following item(s):</div><div><br></div> | | Missing CO detection in 1st floor in Mech Room and Laundry Room by main office |
| 10/6/2026 | | Firealarm15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | Elevator Recall must be connected to Fire Alarm system. |
| 10/5/2026 | | Firealarm14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | 1) System sequencing is not correct. 2) RTU's not connected to system 3) Elevators not connected to system. 4) Sprinkler notification not responding correctly. |