Inspection #: 922394
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final. Wet Mechanical Room and Lobby area.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/5/2026TransferCorrect Below* Miscellaneous corrections from other floors. 
10/5/2026TransferCorrect Below* Corrections from inspection # 92106.Various 1st floor and rooftop corrections not carried forward to this inspection.
10/5/2026TransferCorrect Below* Lobby sconces.Lighting control not complete.
10/5/2026TransferCorrect Below* Lobby floor receptacles.Not installed. No cover on the boxes.
10/5/2026TransferCorrect Below* Lobby chandaliers.Not installed.
10/5/2026TransferCorrect Below* Receptacles on Lobby side of bar.Receptacles within 6ft of sink require GFCI protection.
10/5/2026TransferCorrect Below* Landscape sprinkler controller.No apparent listing mark.
10/5/2026TransferCorrect Below* Mixing valve controller. (Nexa Intellistation)No apparent listing mark.
10/5/2026TransferCorrect Below* Domestic water boost pump, industrial control panel. Floor drain pipe and possibly other piping violates 110.26 working clearances.