| Date | Status | Code | Description | Ref | Location | Comments |
| 10/5/2026 | Transfer | Correct Below | * | | Series rating labelling. | Required per 110.22(C). |
| 10/5/2026 | Transfer | Correct Below | * | | Series ratings between ABB feeder breakers in MSB and branch circuit panels. | Show manufacturer's info showing that ABB feeder breakers will series rate with GE 10K breakers. |
| 10/5/2026 | Transfer | Correct Below | * | | Main switch board. | Label any unused breakers as spare or future. |
| 10/5/2026 | Transfer | Correct Below | * | | Main electrical room snow melt contactors and controllers. | Contactors labelled with a 5KA short circuit current rating. What is the available fault current? Check controller rating. |
| 10/5/2026 | Transfer | Correct Below | * | | Available fault current at branch circuit panels in main electrical room. | Need to establish available fault current values. |
| 10/5/2026 | Transfer | Correct Below | * | | Prep area espresso machines. | Not on site. |
| 10/5/2026 | Transfer | Correct Below | * | | Pass-through between Kitchen and Prep. | Heat lamp not installed. Adjacent receptacle on same circuit not on for testing. |
| 10/2/2026 | Transfer | Correct Below | * | | Large rooftop units, freezer condenser, Captive Air, possibly other. | Various violations of 110.26 working clearances at equipment electrical compartments. Clearances violated by gas lines, condensate lines, curbs, etc. |