Inspection #: 921833
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final inspection. Rooftop and reinspection of corrections from previous inspection #921206. Corrections listed below that are not rooftop issues are outstanding from the previous inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/5/2026TransferCorrect Below* Series rating labelling. Required per 110.22(C).
10/5/2026TransferCorrect Below* Series ratings between ABB feeder breakers in MSB and branch circuit panels.Show manufacturer's info showing that ABB feeder breakers will series rate with GE 10K breakers.
10/5/2026TransferCorrect Below* Main switch board. Label any unused breakers as spare or future.
10/5/2026TransferCorrect Below* Main electrical room snow melt contactors and controllers.Contactors labelled with a 5KA short circuit current rating. What is the available fault current? Check controller rating.
10/5/2026TransferCorrect Below* Available fault current at branch circuit panels in main electrical room.Need to establish available fault current values.
10/5/2026TransferCorrect Below* Prep area espresso machines.Not on site.
10/5/2026TransferCorrect Below* Pass-through between Kitchen and Prep.Heat lamp not installed. Adjacent receptacle on same circuit not on for testing.
10/2/2026TransferCorrect Below* Large rooftop units, freezer condenser, Captive Air, possibly other.Various violations of 110.26 working clearances at equipment electrical compartments. Clearances violated by gas lines, condensate lines, curbs, etc.