Inspection #: 921780
Inspection Type: Mechanical Rough
Inspector: E.Wood
Result: Correction
Comment: The interior of the building is OK for a CCO for fixtures and furnishings, however there is still outstanding mechanical corrections for the pool area, and there is a substantial amount of work being performed by non-mechanical trades in the lobby/ commons areas, and the stairwells.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/25/2026TransferBoilerRough1Installation InstructionsProvide manufacturer's installation instructionsPool heaters (2)Provide install guide, venting methods & materials in question.
9/23/2026TransferBoilerRough 11Relief Valve ThreadsRelief valve discharge piping termination cannot have threads - UPC 608.5Pool heaters (2)Add male adapters or nipples w/ threads cut off of terminal end.