Inspection #: 921368
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include the install of FDs serving FCUs in South 2nd fl mech rm & 1st layer of fire wrap serving rooftop grease duct, OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/25/2026TransferBoilerRough1Installation InstructionsProvide manufacturer's installation instructionsPool heaters (2)Provide install guide, venting methods & materials in question.
9/23/2026TransferBoilerRough 11Relief Valve ThreadsRelief valve discharge piping termination cannot have threads - UPC 608.5Pool heaters (2)Add male adapters or nipples w/ threads cut off of terminal end.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.