| Date | Status | Code | Description | Ref | Location | Comments |
| 10/2/2026 | Transfer | Correct Below | * | | Snow melt contactors and controllers. | Snow melt contactors - labelled with a 5kA short circuit current rating. Check controllers. |
| 10/2/2026 | Transfer | Correct Below | * | | Series rating labelling. | Required per 110.22(C). |
| 10/2/2026 | Transfer | Correct Below | * | | Series ratings between ABB feeder breakers in MSB and branch circuit panels. | Show manufacturer's info showing that ABB feeder breakers will series rate with GE 10K branch circuit breakers. |
| 10/2/2026 | Transfer | Correct Below | * | | Available fault current at panels close to MSB. | Will need to review and establish available fault current values. |
| 10/2/2026 | Transfer | Correct Below | * | | Main Switch Board. | Label any unused breakers as spare or future. |
| 10/1/2026 | Transfer | Correct Below | * | | Receptacles in bar wall cavity. | Require GFCI protection for location within 6ft of sink. |
| 10/1/2026 | Transfer | Correct Below | * | | Prep Area espresso machines. | Not on site. |
| 10/1/2026 | Transfer | Correct Below | * | | Pass-through between kitchen and prep. | Heat lamp not installed. Adjacent receptacle on same circuit not on for testing. |
| 10/1/2026 | Transfer | Correct Below | * | | Cooking line receptacles. | Not GFCI protected. |
| 10/1/2026 | Transfer | Correct Below | * | | Commercial garbage disposal. | Start / stop, disconnect not installed. |
| 10/1/2026 | Transfer | Correct Below | * | | Commercial dishwasher. | Served by a 40A breaker. What is the rated full load? |
| 9/24/2026 | Corrected | Correct Below | * | | Room 141. | Move materials for access. |
| 9/24/2026 | Corrected | Correct Below | * | | Rooms 110 and 139. | Valence lighting, 3-way switches mis-wired. |
| 9/24/2026 | Corrected | Correct Below | * | | Room 109. | Missing receptacle trim plate. |