Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 921092
Inspection Type: Ceiling / Act
Inspector: M.Jellich
Result: Correction
Comment: Seismic at 2nd floor corridor ceiling grid. Requested by: Alex Jansen 5039841183 ajansen@jansenconstructioncompany.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/24/2026TransferACTBACT CorrectionComplete the following corrections :Levels 1 and 4. During my inspection it was observed that multiple perimeter wires were cut during tile installation. We will need access to above ceiling to reinspect these 2 floors. SI has been notified and will have to reinspect as well.
9/24/2026TransferACTBACT CorrectionComplete the following corrections :2nd floor corridorMains running across corridor are pop riveted on both sides of the wall, can only be riveted on one side.
9/24/2026TransferACTBACT CorrectionComplete the following corrections :2nd floor corridorBERC clips only fastened to the drywall. Must be attached to a framing member or wall angle.