Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 921012
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Rough - Approved To include the install of exterior duct related to DHU-1, OK to cover, approved method of FD install serving 2nd fl FCUs, FD install to be inspected at later date. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/25/2026TransferBoilerRough1Installation InstructionsProvide manufacturer's installation instructionsPool heaters (2)Provide install guide, venting methods & materials in question.
9/23/2026TransferBoilerRough 11Relief Valve ThreadsRelief valve discharge piping termination cannot have threads - UPC 608.5Pool heaters (2)Add male adapters or nipples w/ threads cut off of terminal end.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS