Inspection #: 920775
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Progress electrical final covering remaining 2nd, 3rd, and 4th floor issues, plus stairwells and 1st floor guest rooms 101-108. Stairwells progress electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/23/2026TransferCorrect Below* Guest room 107.Room controls malfunctioning.
9/23/2026TransferCorrect Below* Guest room 106.(2) receptacle trim plates missing.
9/23/2026TransferCorrect Below* Guest rooms 101 and 102.Bathroom switches missing.
9/23/2026TransferCorrect Below* Fan coil units being retrofitted with electric heating elements.1. Determine full load of fan coil units and field installed heat elements to determine proper circuit size. 2. Drawings show many FCU circuits as #10 conductors protected by 35A breakers. 3. Show instructions permitting the installation of heating elements.
9/23/2026TransferCorrect Below* 4th floor panel M3.Heat trace breakers require breaker locks