| Date | Status | Code | Description | Ref | Location | Comments |
| 9/23/2026 | Transfer | Correct Below | * | | Guest room 107. | Room controls malfunctioning. |
| 9/23/2026 | Transfer | Correct Below | * | | Guest room 106. | (2) receptacle trim plates missing. |
| 9/23/2026 | Transfer | Correct Below | * | | Guest rooms 101 and 102. | Bathroom switches missing. |
| 9/23/2026 | Transfer | Correct Below | * | | Fan coil units being retrofitted with electric heating elements. | 1. Determine full load of fan coil units and field installed heat elements to determine proper circuit size. 2. Drawings show many FCU circuits as #10 conductors protected by 35A breakers. 3. Show instructions permitting the installation of heating elements. |
| 9/23/2026 | Transfer | Correct Below | * | | 4th floor panel M3. | Heat trace breakers require breaker locks |