Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 919128
Inspection Type: Ceiling Rough Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2026 EC1Correct Below Pool equipment.(3) 208V 3-phase pump motors, (2) 208V gas-fired pool heaters, other misc. pool equipment. Contractor could not produce a drawing or change order that shows these branch circuits or equipment. The pool pumps do not appear to incorporate thermal protection; no running overload protection installed. 3-phase pool pumps are currently running on (3) 20A, 1-pole GFCI breakers. Contractor needs to show engineering for the installed pool equipment. Possibly other pool equipment issues.
9/9/2026 EC1Correct Below Meeting Room T-bar grid ceiling.Envision recessed, remodel style luminaires with spring-loaded clips cannot be supported from acoustical ceiling tile. Envision makes a "Universal Mounting Plate" apparently for this situation. Will also require seismic wires.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS