Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 918987
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include inspection of RTUs w/ related deferred submittals, & flex/GRDs serving kitchen, OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/31/2026TransferMechRgh2Provide FSD Install GuideProvide fire/smoke damper installation instructions IMC 607.2Kitchen FSDsFSDs covered prior to inspection of framing, sheetrock tight to dampers. Cut sheetrock back to required distance for verification that framing has been installed to required specs.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS