Inspection #: 918570
Inspection Type: Mechanical Rough
Inspector: E.Wood
Result: Partial
Comment: Last bit of grease duct weld test for end cap, Approved. OK for the 1st layer of grease wrap.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/31/2026TransferMechRgh2Provide FSD Install GuideProvide fire/smoke damper installation instructions IMC 607.2Kitchen FSDsFSDs covered prior to inspection of framing, sheetrock tight to dampers. Cut sheetrock back to required distance for verification that framing has been installed to required specs.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.