Inspection #: 917802
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved Grease duct light test approved serving all remaining incomplete welds excluding North endcap related to horizontal duct above hood. Corrections remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/31/2026TransferMechRgh2Provide FSD Install GuideProvide fire/smoke damper installation instructions IMC 607.2Kitchen FSDsFSDs covered prior to inspection of framing, sheetrock tight to dampers. Cut sheetrock back to required distance for verification that framing has been installed to required specs.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.