Inspection #: 917438
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Partial electrical final inspection of 2nd, 3rd, and 4th floor Mech Rooms, IT Rooms, Electrical Rooms, Laundry Rooms, etc. Also, 2nd floor corridor. NOTE: Stairs not complete at this time.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/21/2026TransferCorrect Below* Fan coil units - various Mech Rooms.Equipment installed currently require 15A circuits. Original design shows larger equipment? Will require change order by final.
9/21/2026TransferCorrect Below* 2nd floor ice machine receptacles.1. Not GFCI protected? 2. One receptacle dead? 3. Check 4th floor ice machine circuits for GFCI protection.
9/21/2026TransferCorrect Below* 2nd floor Mech Room.Circuits serving receptacles not properly identified.
9/21/2026TransferCorrect Below* 2nd floor panel 2A.Room 210, circuit 2 AFCI will not reset.
9/21/2026TransferCorrect Below* Unit 330 breaker. AFCI device tripping and will not reset.
9/21/2026TransferCorrect Below* All panels.1. Panel schedules not completely correct. 2. Label all unused breakers as spares. 3. Breaker designations for rooftop equipment needs to include location or other identifying information.
9/21/2026TransferCorrect Below* 4th floor panel M3.Heat trace breakers require breaker locks.
8/27/2026TransferCorrect Below* Room 202B Not complete.
8/21/2026TransferCorrect Below* Room 227.Cove lighting not complete.