Inspection #: 916045
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Rough - Approved To include inspection of rooftop ducting related to MAUs & RTUs, OK to cover. See correction.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/31/2026CorrectedMechRgh2Provide FSD Install GuideProvide fire/smoke damper installation instructions IMC 607.2Kitchen FSDsFSDs covered prior to inspection of framing, sheetrock tight to dampers. Cut sheetrock back to required distance for verification that framing has been installed to required specs.
8/19/2026TransferMechRghSee commentsSee Inspector CommentsGrease duct.COs required per 2018 IMC.