Inspection #: 915815
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: 3rd floor rooms 301 - 328 plug test and lighting test. Also 3rd floor corridor. This inspection plus previous inspection #915193 completes 3rd floor guest rooms and corridors. Progress electrical final for 3rd floor guest rooms and corridors approved. NOTE: 3rd and 4th floor electrical rooms, laundry or other similar areas not yet final inspected.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/18/2026TransferCorrect Below*  1. underground splice for neutral and grounds required to be rated for wet location. 2. Bond metal lid with #6, subject to damage. 3. Missing screws at hand hole covers.