Inspection #: 914730
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Rough - Approved Grease duct light test approved from horizontal-vertical flange & all horizontal duct from vertical to 2nd 45 heading towards hood, OK to cover. See correction. NOTE: Grease duct incomplete from hood to 45 flange.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/20/2026TransferMechRghSee commentsSee Inspector CommentsGrease ductAs per 2018 IMC 506.3.8 & 506.3.9 COs required. At minimum 1-CO required between horizontal 45s, 1-CO 10' max on vertical from horizontal-vertical 90 & every 20' from there.
6/15/2026CorrectedBoilerRough 20BVENT SupportB-Vent is not properly supported- per manufacture install guide, IFGC 506.2 and UPC 510.7.6 (S/W)DVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026CorrectedMechRghSee commentsSee Inspector CommentsDVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026CorrectedMechRghSee commentsSee Inspector CommentsDVFP ventingScrews shall not penetrate inner wall of B-vent. Provide tool to remove screw(s) for inspection of screw penetration. If screws have penetrated inner wall, replacement of compromised B-vent required.
6/15/2026CorrectedMechRgh25Fireplace Install InstructionsProvide installation instructions for fireplaceDVFP power venterInstall guide shall be onsite for review during inspection.