Inspection #: 914594
Inspection Type: Refrigeration Final
Inspector: N.Jackson
Result: Correction
Comment: Refrigeration Final partial pass. See Correction. CCO for contractors and staff from 09/30/2026 to 11/30/2026. Note: Deferred submittals provided for wall freezers equipment. Note: Refrigerant gas sensors installed, calibrated, and functioning.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/5/2026TransferRefrigRghCommentsSee Inspector CommentsRefrigerant Declaration Letter<div>Declaration. A certificate of test shall be provided for</div><div>all systems containing 55 pounds (25 kg) or more of refrigerant.</div><div>The certificate shall give the name of the refrigerant and</div><div>the field test pressure applied to the high side and the low side</div><div>of the system. The certification of test shall be signed by the</div><div>installer and shall be made part of the public record. 2018 IMC Section 1108.4</div>
10/1/2026TransferRefrigRghCommentsSee Inspector Comments1074 N Muldoon RdDomestic hot water branch not completed as shown on plans pg. R4.3.&nbsp;&nbsp;