Inspection Type: Ceiling Rough Electrical
Inspector: M.Green
Result: Correction
Comment: Electrical ceiling rough approved - 1st floor Lounge, Meeting Room, Kitchen Storage. Also, comments regarding pool equipment.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2026TransferEC1Correct Below Pool equipment.(3) 208V 3-phase pump motors, (2) 208V gas-fired pool heaters, other misc. pool equipment. Contractor could not produce a drawing or change order that shows these branch circuits or equipment. The pool pumps do not appear to incorporate thermal protection; no running overload protection installed. 3-phase pool pumps are currently running on (3) 20A, 1-pole GFCI breakers. Contractor needs to show engineering for the installed pool equipment. Possibly other pool equipment issues.
9/9/2026TransferEC1Correct Below Meeting Room T-bar grid ceiling.Envision recessed, remodel style luminaires with spring-loaded clips cannot be supported from acoustical ceiling tile. Envision makes a "Universal Mounting Plate" apparently for this situation. Will also require seismic wires.