Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 913917
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include the install of FSDs in kitchen & West end chase serving S/A, E/A & Makeup air ducting. NOTE: Framing incomplete related to kitchen FSDs.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/20/2026TransferMechRghSee commentsSee Inspector CommentsGrease ductAs per 2018 IMC 506.3.8 & 506.3.9 COs required.
6/15/2026CorrectedBoilerRough 20BVENT SupportB-Vent is not properly supported- per manufacture install guide, IFGC 506.2 and UPC 510.7.6 (S/W)DVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026CorrectedMechRghSee commentsSee Inspector CommentsDVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026CorrectedMechRghSee commentsSee Inspector CommentsDVFP ventingScrews shall not penetrate inner wall of B-vent. Provide tool to remove screw(s) for inspection of screw penetration. If screws have penetrated inner wall, replacement of compromised B-vent required.
6/15/2026CorrectedMechRgh25Fireplace Install InstructionsProvide installation instructions for fireplaceDVFP power venterInstall guide shall be onsite for review during inspection.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS