| Date | Status | Code | Description | Ref | Location | Comments |
| 9/9/2026 | | FireSprinkRoughOther1 | Fire Sprinkler Rough Approved | Fire Sprinkler Rough Approved | 1st and 4th floor | All okay and complete rough for system |
| 8/4/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | Lobby area | Okay to cover areas of lobby |
| 7/24/2026 | | FireSprinkRough9 | Correction(s) #5 | Correct the following item(s): | 3rd floor | <strong data-start="603" data-end="938">Revise the CPVC sway bracing to comply with the manufacturer's installation requirements. Conventional longitudinal braces that apply compressive loads directly to CPVC piping are not permitted. Install approved longitudinal and lateral bracing in accordance with the manufacturer's installation instructions and NFPA 13.</strong> |
| 7/24/2026 | | FireSprinkRough10 | Correction(s) #6 | Correct the following item(s): | 3rd floor | Provide separation between electrical wiring and CPVC sprinkler piping. |
| 7/21/2026 | | FireSprinkRough2 | Correction(s) #2 | Correct the following item(s): | 3rd and 4th floor corridor | <p class="MsoNormal" style="font-size: 12px; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial; margin-bottom: 0in; line-height: 13.5pt; display: inline !important;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:"Times New Roman";
color:black;mso-color-alt:windowtext;mso-font-kerning:0pt;mso-ligatures:none">The
hydrostatic tests and rough in inspection have passed on both the 3rd and 4th
floors. Based on the current status, we can issue a Conditional Certificate of
Occupancy (CCO) for the installation of furniture and fixtures on those floors
while the project continues toward final completion.</span><o:p></o:p></p><p class="MsoNormal" style="font-size: 12px; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial; margin-bottom: 0in; line-height: 13.5pt;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:"Times New Roman";
color:black;mso-color-alt:windowtext;mso-font-kerning:0pt;mso-ligatures:none">The
following conditions will apply:</span><o:p></o:p></p><ul type="disc"><li class="MsoNormal" style="line-height: normal; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:
"Times New Roman";color:black;mso-color-alt:windowtext;mso-font-kerning:
0pt;mso-ligatures:none">No storage of any kind is permitted in the
corridors. This includes furniture awaiting installation, cardboard boxes,
packing materials, trash, or any other stored items.</span><o:p></o:p></li><li class="MsoNormal" style="line-height: normal; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:
"Times New Roman";color:black;mso-color-alt:windowtext;mso-font-kerning:
0pt;mso-ligatures:none">All bedroom doors shall remain closed at all times
during the furniture installation process.</span><o:p></o:p></li><li class="MsoNormal" style="line-height: normal; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:
"Times New Roman";color:black;mso-color-alt:windowtext;mso-font-kerning:
0pt;mso-ligatures:none">Once the parts arrive to repair the sprinkler
bracing deficiency, a fire watch will be required anytime the sprinkler
system is taken out of service to complete the repairs.</span><o:p></o:p></li><li class="MsoNormal" style="line-height: normal; background-image: initial; background-position: initial; background-size: initial; background-repeat: initial; background-attachment: initial; background-origin: initial; background-clip: initial;"><span style="mso-fareast-font-family:"Times New Roman";mso-bidi-font-family:
"Times New Roman";color:black;mso-color-alt:windowtext;mso-font-kerning:
0pt;mso-ligatures:none">If corridor storage is observed at any time, or if
these conditions are not maintained, the CCO will be revoked.</span><o:p></o:p></li></ul><p style="font-size: 12px;"></p><p class="MsoNormal" style="font-size: 12px;"><o:p> </o:p></p> |
| 6/22/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | North Covered Area only | All okay to proceed. |
| 6/11/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st Floor Pool, Gym and bathrooms | All okay to proceed. |
| 6/4/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st floor main hall and public bathrooms | Okay to proceed. |
| 5/19/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st floor rooms only | 1st floor rooms are okay to cover. |
| 3/17/2026 | | FireSprinkRough10 | Correction(s) #6 | Correct the following item(s): | 2nd floor hall | provide and maintain required space between Duct and sprinkler piping. |
| 3/17/2026 | | FireSprinkRough1 | Correction(s) #1 | Correct the following item(s): | 2nd floor hall | Provide information for compatibility with CPVC piping. |
| 3/17/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 2nd floor only | okay to cover rooms only, Hall has correction. |
| 1/15/2026 | | FireSprinkRough11 | Notes | Notes: | | ADVISORY - Main piping runs along the length of the corridor could be subject to significant thermal expansion. Adjust piping and branch line penetrations as necessary // PANILO |