| Date | Status | Code | Description | Ref | Location | Comments |
| 8/4/2026 | Transfer | firesprinkl13 | CCO Approved | CCO approved for fire sprinkler system | 2nd and 3rd floors | okay for C.C.O. for FF&E Furniture loading in rooms only. |
| 1/12/2026 | Transfer | firesprinklr14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | <h2><p class="MsoNormal"><span style="font-weight: normal;">Sprinkler system components shall not be used to support
nonsprinkler system components. Other disciplines cannot be supported by
the sprinkler system. NFPA 13 Section 4.9.</span><o:p></o:p></p></h2> |
| 1/12/2026 | Transfer | firesprinkl15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | Anything touching the CVPC mush be checked for compatibility with the Blaze Master Instillation instructions. |
| 1/12/2026 | Transfer | firesprinkl16 | Correction(s) #3 | <div>Correct the following item(s):</div><div><br></div> | | <p data-start="63" data-end="225"><strong data-start="63" data-end="223">Hangers shall be installed in accordance with the manufacturer’s installation instructions and shall not have rough or sharp edges in contact with the pipe.</strong></p>
<p data-start="232" data-end="439" data-is-last-node="">The hangers observed in <strong data-start="256" data-end="268">Room 336</strong> are not the approved type. <strong data-start="296" data-end="439" data-is-last-node="">Verify that all pipe hangers in this area are correct and replace as necessary to comply with the manufacturer’s installation requirements.</strong></p> |