Inspection #: 910439
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Plug test and lighting test.. Remainder of 4th floor, odd numbered guest rooms 421 - 427. Many corrections similar to previous guest room finals. NOTE: contractor used a battery to power the room control system to enable lighting and controlled receptacles. Also, 3rd floor Linen Hall and adjacent Ice Room sheetrock ceilings electrical rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/15/2026TransferCorrect Below* Most units.Low voltage cove lighting not installed.
7/15/2026TransferCorrect Below* All units.P-tac room units not complete.
7/15/2026TransferCorrect Below* All units T-stats.Not installed. T-stat powered from p-tac room unit controls lights and controlled receptacles.
7/15/2026TransferCorrect Below* Units 423 and 425.Missing receptacle trim plates.
7/15/2026TransferCorrect Below* Units 441 - 437.Malfunctioning control RIBs.