Inspection #: 909936
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: 4th floor guest rooms - south side of corridor - even numbers 402 - 442. Plug test and lighting test. NOTE Contractor used a battery to power the room control system to enable lighting and controlled receptacles. Also, sheetrock ceilings electrical rough at 4th floor Elevator Lobby, Ice Room, Linen Corridor approved. Corrections similar to previous 4th floor plug and lighting test.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/14/2026TransferCorrect Below* Unit 434.TV receptacle missing trim.
7/14/2026TransferCorrect Below* Unit 428 below T-stat.Receptacle device missing.
7/14/2026TransferCorrect Below* Units 404 and 412.Bath fan covered by sheetrock.
7/10/2026TransferCorrect Below* All units.Low voltage cove lighting not installed.
7/10/2026TransferCorrect Below* All units.P-tac room units not complete.
7/10/2026TransferCorrect Below* Unit 419.Controlled receptacle on right side of bed - 1/2 not hot.
7/10/2026TransferCorrect Below* Unit 415.Breaker tripped.
7/10/2026TransferCorrect Below* All unit bathrooms - 401 to 419. Receptacle for lighted mirror requires readily accessible GFIC protection (in addition to AFCI protection).
7/10/2026TransferCorrect Below* All units T-stats.Not installed. T-stat powered from P-tac room unit controls lights and controlled receptacles.