Inspection #: 909634
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: 4th floor units 401, 403, 405, 409, 411, 413, 415, 417, 419 - plug and lighting tested. NOTE: Contractor had to use a battery to power the room control system to enable lighting and controlled receptacles.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/10/2026TransferCorrect Below* All units.Low voltage cove lighting not installed.
7/10/2026TransferCorrect Below* All units.P-tac room units not complete.
7/10/2026TransferCorrect Below* Unit 419.Controlled receptacle on right side of bed - 1/2 not hot.
7/10/2026TransferCorrect Below* Unit 415.Breaker tripped.
7/10/2026TransferCorrect Below* All unit bathrooms.Receptacle for lighted mirror requires readily accessible GFIC protection (in addition to AFCI protection).
7/10/2026TransferCorrect Below* All units T-stats.Not installed. T-stat powered from P-tac room unit controls lights and controlled receptacles.