Inspection #: 908069
Inspection Type: Plumbing Rough
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2026 GasPipeComSee comments RTU intakes As per 2018 IMC 401.4 intakes shall be located not less than 10' from gas regulator vents.
6/29/2026 GasRgh14PipingSee commentssee commentsRooftop gas regulatorsAs per local amendment to 2018 IFGC 410.6 regulator shall be installed 2' above the roof.
4/14/2026 PlumbRgh14CommentsSee Inspectors CommentsTo include but not limited to H & CW serving pool restrooms & kitchenAs per 2018 UPC 609.10 hammer arrestors required to serve quick closing valves.
4/14/2026 GasRgh14PipingSee commentssee commentsMedium pressure gas requlatorsAs per 2018 IFGC 410.2 note 6 tee fitting shall be installed 10 pipe diameters downstream of regulator outlet.