| Date | Status | Code | Description | Ref | Location | Comments |
| 6/29/2026 | | GasPipeCom | See comments | | RTU intakes | As per 2018 IMC 401.4 intakes shall be located not less than 10' from gas regulator vents. |
| 6/29/2026 | | GasRgh14Piping | See comments | see comments | Rooftop gas regulators | As per local amendment to 2018 IFGC 410.6 regulator shall be installed 2' above the roof. |
| 4/14/2026 | | PlumbRgh14 | Comments | See Inspectors Comments | To include but not limited to H & CW serving pool restrooms & kitchen | As per 2018 UPC 609.10 hammer arrestors required to serve quick closing valves. |
| 4/14/2026 | | GasRgh14Piping | See comments | see comments | Medium pressure gas requlators | As per 2018 IFGC 410.2 note 6 tee fitting shall be installed 10 pipe diameters downstream of regulator outlet. |