| Date | Status | Code | Description | Ref | Location | Comments |
| 6/22/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | North Covered Area only | All okay to proceed. |
| 6/11/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st Floor Pool, Gym and bathrooms | All okay to proceed. |
| 6/4/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st floor main hall and public bathrooms | Okay to proceed. |
| 5/19/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 1st floor rooms only | 1st floor rooms are okay to cover. |
| 3/17/2026 | | FireSprinkRough10 | Correction(s) #6 | Correct the following item(s): | 2nd floor hall | provide and maintain required space between Duct and sprinkler piping. |
| 3/17/2026 | | FireSprinkRough1 | Correction(s) #1 | Correct the following item(s): | 2nd floor hall | Provide information for compatibility with CPVC piping. |
| 3/17/2026 | | FireSprnkRoughOther | Fire Sprinkler Rough Partial Approval | Fire Sprinkler Rough Partial Approval. List area(s) approved | 2nd floor only | okay to cover rooms only, Hall has correction. |
| 1/15/2026 | | FireSprinkRough11 | Notes | Notes: | | ADVISORY - Main piping runs along the length of the corridor could be subject to significant thermal expansion. Adjust piping and branch line penetrations as necessary // PANILO |