| Date | Status | Code | Description | Ref | Location | Comments |
| 6/15/2026 | Transfer | BoilerRough 20 | BVENT Support | B-Vent is not properly supported- per manufacture install guide, IFGC 506.2 and UPC 510.7.6 (S/W) | DVFP venting | Support venting per manufacturer's required intervals. |
| 6/15/2026 | Transfer | MechRgh | See comments | See Inspector Comments | DVFP venting | Support venting per manufacturer's required intervals. |
| 6/15/2026 | Transfer | MechRgh | See comments | See Inspector Comments | DVFP venting | Screws shall not penetrate inner wall of B-vent. Provide tool to remove screw(s) for inspection of screw penetration. If screws have penetrated inner wall, replacement of compromised B-vent required. |
| 6/15/2026 | Transfer | MechRgh25 | Fireplace Install Instructions | Provide installation instructions for fireplace | DVFP power venter | Install guide shall be onsite for review during inspection. |