Inspection #: 906623
Inspection Type: Mechanical Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include the install of S & T/A FSDs serving linen area related to 4th fl, S/A FSDs & remaining tie in to mains in corridor related to 3rd fl & S/A corridor mains w/ branch connections within grid lines 1-10 on 1st fl, OK to cover. NOTE: 1st fl S/A FSD on grid line 5 not installed.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/15/2026TransferBoilerRough 20BVENT SupportB-Vent is not properly supported- per manufacture install guide, IFGC 506.2 and UPC 510.7.6 (S/W)DVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026TransferMechRghSee commentsSee Inspector CommentsDVFP ventingSupport venting per manufacturer's required intervals.
6/15/2026TransferMechRghSee commentsSee Inspector CommentsDVFP ventingScrews shall not penetrate inner wall of B-vent. Provide tool to remove screw(s) for inspection of screw penetration. If screws have penetrated inner wall, replacement of compromised B-vent required.
6/15/2026TransferMechRgh25Fireplace Install InstructionsProvide installation instructions for fireplaceDVFP power venterInstall guide shall be onsite for review during inspection.