Inspection #: 906553
Inspection Type: Final Mechanical
Inspector: E.Wood
Result: Correction
Comment: We need the fireplace venting reinspected. Call 1 hour before inspection so we can have someone there. Requested by: Jason Magers 907-395-7288 officemanager@handhsheetmetal.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/18/2026CorrectedMechFinalSee commentsSee Inspector CommentsThe permit.Please add H and H sheet metal to the permit with a limited scope of fireplace installation and venting.
6/18/2026TransferMechFinalSee commentsSee Inspector CommentsThe fireplace.Per the manufacturer's installation instructions page 18 "Above Unit" "A minimum of 19" of non combustible facing material ( concrete backer board etc.) must be used above the fire box opening.